Manual 2100-674A
Page
24 of 41
Additional LV1000 Connections
There are factory-installed jumpers across terminals #8 and #9 (smoke detector), #10 and #11 (hydrogen detector)
and #12 and #13 (generator run). Remove the factory-installed jumpers before connecting to the detectors and/or
generator (if applicable).
INPUTS
LV1000 Connections
Sensor Connections
Description
Wire Mark
Terminal
Terminal
Smoke
DI1
8
Varies
Smoke Detector Input
GND
9
Ground
Hydrogen
DI2
10
Hydrogen Detector Input
GND
11
Ground
Generator
DI3
12
Generator Run Input
GND
13
Ground
Anti-Theft
DI4
14
9 (BG1000)
Anti-Theft Device
GND
15
10 (BG1000)
Ground
Power Loss
Relay - A1
Varies
230VAC Power Loss Relay
Relay - A2
230VAC Power Loss Relay
OUTPUTS
LV1000 Connections
External
Connections
Description
Wire Mark
Terminal
Terminal
Humidifier
NO1
34
Varies
Humidifier Output
C1
35
Common
HVAC Fail
NO2
36
Alarm Relay – HVAC Fail
C1
37
Common
HVAC Maintenance
NO3
38
Alarm Relay –
HVAC Maintenance
C1
39
Common
Anti-Theft
NO4
40
Alarm Relay – Anti-Theft
C2
41
Common
COMMUNICATIONS
LV1000 Connections
External
Connections
Description
Wire Mark
Terminal
Terminal
Fieldbus 1*
FB-1 (–)
42
2
Wall Unit Daisy Chain
FB-1 (+)
43
1
Wall Unit Daisy Chain
Fieldbus 2*
FB-2 (–)
44
–
IPv6 SNMP Board
FB-2 (+)
45
+
Ground
Ground
FB-2 (–)
46
Drain
Drain for Daisy Chain
* Polarity Sensitive