Installing Remote Indoor Temperature/Humidity Sensor(s)
One remote indoor temperature/humidity sensor and 35' of 18 gauge 5-conductor shielded cable is included with the
controller. This sensor must be installed for proper operation. Mount the temperature/humidity sensor in a location
least likely to be affected by open doors, rack-mounted fans, radiant heat sources, etc. Location height should be
approximately 60" above the floor. The sensor should be installed on a 2" x 4" junction box to allow for control wire
conduit (see Figure 19). Use shielded cable to connect to controller.
FIGURE 19
Remote Indoor Temperature/Humidity Sensor Installation
1. Connect wires from the 18 gauge shielded cable to terminals #24, #25, #18, #19 and #30.
2. Connect the other end of the shielded cable to the sensor
terminals. Be sure wires are connected to proper terminals
as shown in table above. Sensor jumpers need to be
positioned for 0-1 V. With sensor oriented as shown in
image to right, move both jumpers to left position (DP1 and
DP2 set to OFF).
This applies to all temperature/humidity sensors connected
to the LV controller.
Sensor is best mounted on a junction box, and it is
recommended that the cable be in conduit.
TB#
Sensor
Description
Wire
Mark
24
NTC OUT Indoor Temperature 1
B6
25
NTC OUT Ground
GND
18
OUT H
Indoor Humidity 1 Signal: 0-1 VDC
B2
19
M (G)
Indoor Humidity 1 Common
GND
30
+ (G)
Indoor Humidity 1 Power
+VDC
Jumper
LV1000 Terminal Block