1. Route the cable from the first wall-mount unit to the
terminal block of the second wall-mount unit. If this is
the last unit to be connected, make a small service loop
and attach EMI filter as shown.
FIGURE 26
Communication Wiring: Termination at Additional Wall-Mount Units
2. Connect the wires matching the terminal
designations (+/-) of the controller terminals.
Cap the loose drain with a wire nut or
electrical tape.
3. Continue daisy chaining units by connecting
"+" to "+", "-" to "-" and wire nutting drain
together until last unit which is capped with
a wire nut.
Attach EMI filter as shown above
at last unit.
Up to four wall-mount units can
be connected and controlled by one LV1000
controller.