Up to two additional temperature/humidity sensors may be added.
Be sure the sensors are connected to the proper
terminals on the terminal block and sensor as listed below.
See page 22 for information on correct sensor jumper
position.
FIGURE 20
Additional Remote Temperature and Temperature/Humidity Sensor Installation
Up to two additional temperature and humidity sensors can be purchased and installed. Alternately, temperature-
only sensors can be purchased and installed instead of the combination sensors. Use shielded cable to connect
additional sensors to controller.
Optional Remote
Temperature/Humidity Sensor
Terminals 28, 29, 22, 23 & 32
TB#
Sensor
Description
Wire
Mark
28
NTC OUT Indoor Temperature 3
B8
29
NTC OUT Ground
GND
22
OUT H
Indoor Humidity 3 Signal: 0-1 VDC
B4
23
M (G)
Indoor Humidity 3 Common
GND
32
+ (G)
Indoor Humidity 3 Power
+VDC
Optional Remote
Temperature/Humidity Sensor
Terminals 26, 27, 20, 21 & 31
TB#
Sensor
Description
Wire
Mark
26
NTC OUT Indoor Temperature 2
B7
27
NTC OUT Ground
GND
20
OUT H
Indoor Humidity 2 Signal: 0-1 VDC
B3
21
M (G)
Indoor Humidity 2 Common
GND
31
+ (G)
Indoor Humidity 2 Power
+VDC
Temperature-only sensors can be used in place of the additional temperature/humidity sensors. #2 temperature-only sensor
will connect to TB# 26 and 27. #3 temperature-only sensor will connect to TB# 28 and 29. The wire connections for the
temperature-only sensors are not polarity sensitive.