Manual 2100-674A
Page
37 of 41
To enable/disable
Indoor Humidity 2
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Indoor
Humidity 2 (C4)
.
5) Press ENTER key to scroll to
Enable
(see
Figure 40).
FIGURE 40
Configuring Indoor Humidity 2 Sensor
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
To enable/disable
Indoor Humidity 3
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Indoor
Humidity 3 (C5)
.
5) Press ENTER key to scroll to
Enable
(see
Figure 41).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 41
Configuring Indoor Humidity 3 Sensor
To enable/disable
Indoor Temperature 1
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
FIGURE 39
Configuring Indoor Humidity 1 Sensor
5. Configure Sensors
The system will need to be configured for the
number of temperature and humidity sensors
installed. The system is shipped with one
combination temperature and humidity sensor.
Additional combination sensors may be purchased
or alternatively, temperature-only sensors may be
purchased instead. The LV is capable of utilizing
three temperature sensors and three humidity
sensors. The system will need to be configured for
the various configurations.
If necessary, the sensors could be calibrated at this
time too. For information on calibrating the sensors
(adjusting the offset), see page 40.
To enable/disable
Indoor Humidity 1
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Indoor
Humidity 1 (C3)
.
5) Press ENTER key to scroll to
Enable
(see
Figure 39).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).