GENERAL INFORMATION
Air Conditioning System
This Bard air conditioning system is composed of
FUSION-TEC WR Series wall-mounted air conditioners
matched with an LC6000 lead/lag controller. The wall
mounts are specifically engineered for telecom/motor
control center rooms.
NOTE:
The LC6000 lead/lag controller and FUSION-
TEC WR Series wall-mount units are designed
specifically to work together. The controller
cannot run other Bard models or other brands of
systems, nor can other controllers run the WR
Series wall-mount units. They are a complete
system, and must be used together.
Wall-Mount Air Conditioner Units
The Fusion-TEC WR Series wall-mount units operate on
VAC power. The units will supply 100% of rated cooling
airflow in free cooling mode with ability to exhaust
the same amount through the unit itself without any
additional relief openings in the shelter.
Each of these units are fully charged with refrigerant
and may have optional auxiliary heat.
Controller
LC6000 controller and accessories are shown below.
1
One remote temperature/humidity sensor is included with the LC6000 controller. If the site in which the LC6000
controller will be used has more than one zone (maximum three zones per LC6000), additional remote temperature/
humidity sensors (one sensor per zone) will need to be purchased and installed in the additional zones. One
additional temperature-only sensor (Bard P/N 8301-058) may also be used in Zone 1 but will also need to be
purchased separately. Additional temperature/humidity sensors require field-supplied 5-wire 18 gauge shielded
cable. Temperature-only sensors require field-supplied 2-wire 18 gauge shielded cable.
(1) LC6000 Programmable Logic
Controller
Outside Air
Temperature/Humidity Sensor
Bard P/N 8301-090
(2) Communication EMI Filters
Bard P/N 8301-055
(1) TEC-EYE
TM
Hand-Held Diagnostic Tool
Bard P/N 8301-059
(1) Remote Temperature/Humidity Sensor
1
Bard P/N 8403-079
(1) 35' 5-Wire 18 Gauge Shielded Cable
Remote
Temperature Only Sensor
Bard P/N 8301-058
Optional Sensors:
+
Remote
Temperature/Humidity Sensor
1
Bard P/N 8403-079
LC6000-200 Series Controller and Accessories Included with Controller
Содержание FUSION-TEC WR Series
Страница 2: ......
Страница 50: ......
Страница 53: ......
Страница 63: ......
Страница 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 75: ......
Страница 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Страница 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Страница 96: ......
Страница 100: ......