Manual 2100-704C
Page
34 of 47
FIGURE 32
LC6000 Controller Supply Wiring
Supply Wiring
The LC6000 controller is powered by 120, 208 or 240 volts from the shelter. Field-supplied supply wiring should
be minimum 16 gauge, maximum 14 gauge (see Figure 32). A reliable earth ground must be connected in addition
to any grounding from conduit. Grounding bolts and nuts are included with the controller for this purpose; a 2 hole
grounding lug must be field supplied. Install as shown in Figure 33.
Failing to ground the controller box properly
could result in damage to the equipment.
FIGURE 33
Controller Grounding Posts
5
7
9
17
19
21
25
23
27
29
31
35
33
37
11
13
15
39
43
41
45
47
51
49
53
55
59
57
60
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
1
2
3
4
120
VAC
Input
(L1)
208V
VAC
Input
(L1)
240V
VAC
Input
(L1)
Power
Input
Common
(L2 or N)
Power
Input
Ground
A reliable earth ground must be connected in
addition to any grounding from conduit. Attach
earth ground to side of controller box using bolts
and nuts supplied with controller and field-
supplied 2 hole grounding lug.
Failing to ground
the controller box properly could result in damage
to the equipment.
Содержание FUSION-TEC WR Series
Страница 2: ......
Страница 50: ......
Страница 53: ......
Страница 63: ......
Страница 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 75: ......
Страница 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Страница 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Страница 96: ......
Страница 100: ......