Manual 2100-704C
Page
40 of 47
After each of the wall-mount units have been
addressed, had a run test performed and had the alarm
logs cleared, the rest of the system set up can proceed.
Setting Up LC6000 for Operation
The LC6000 controller will be used for the remaining
steps in the set up process.
LC6000 Status Screen
The Status screen is the default start-up screen and
also the return screen after 5 minutes of no activity on
the LC6000. The screen can be accessed any time by
pressing the ESCAPE key repeatedly.
The Status screen on the LC6000 displays the current
date, time, unit displayed, zones and system status
(see Figure 44).
4. Set LC Controller Date and Time
1)
Press MENU key to access the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press the UP or DOWN keys to scroll to the
Settings
menu; press ENTER key.
4) Press UP or DOWN keys to scroll to
Date/Time
menu; press ENTER key.
5) Press UP or DOWN keys to scroll to
Date/Time
change
.
6) Press ENTER key to scroll to the desired value
to be changed (see Figure 43).
7) Press UP or DOWN keys to change the value.
8) Press ENTER key to save and to scroll to top
of screen.
9) Press UP or DOWN keys to scroll to
Timezone
(if applicable). Follow steps 6-8 to change
timezone.
10) Press ESCAPE key several times to return to
Main Menu screen.
NOTE:
The LC6000 will sync the time and date
configured to each of the wall-mount units once
communication is established.
FIGURE 43
Setting Controller Date and Time
FIGURE 44
LC6000 Controller Display and Interface (Status Screen Shown)
LC6000 interface
key functions are the
same as those shown
for the TEC-EYE in
Figure 36 on page 37.
DOWN KEY
ALARM KEY
MENU KEY
UP KEY
ENTER KEY
ESCAPE KEY
5. Configure Sensors
The system will need to be configured for the
number of temperature and humidity sensors
installed. The system is shipped with one
combination temperature and humidity sensor.
Additional combination sensors may be purchased
or alternatively, temperature-only sensors may be
purchased instead. The LC is capable of utilizing
five temperature sensors and four humidity sensors.
The system will need to be configured for the
various configurations.
If necessary, the sensors could be calibrated at this
time too. For information on calibrating the sensors
(adjusting the offset), see page 45.
To enable/disable
Zone 1 Indoor Humidity
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Z1 Indoor
Hum C4
.
5) Press ENTER key to scroll to
Enable
(see
Figure 45).
Содержание FUSION-TEC WR Series
Страница 2: ......
Страница 50: ......
Страница 53: ......
Страница 63: ......
Страница 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 75: ......
Страница 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Страница 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Страница 96: ......
Страница 100: ......