FIGURE 30
Communication Wiring: Termination at the First Wall-Mount Unit
1. From the controller, extend the shielded cable through a separate conduit
and route to the provided terminal block next to the wall-mount control
board.
These connections are polarity-sensitive. Two-wire communication from
control board is prewired to terminal block. Make sure to match "+" and "-"
symbols on controller terminal block.
2. Connect the wires matching the terminal
designations (+/-) of the controller
terminals. Leave the drain wire loose.
3. Connect another cable in a similar
fashion (“daisy chain”) to route in
conduit to the second wall-mount unit.
Connect both drain wires with wire nut.
From LC6000
Controller
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 1 Terminal Block
From LC6000
Controller
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 1 Terminal Block
To Wall-Mount Unit 2
From LC6000
Controller
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 1 Terminal Block
Wall-Mount Unit 1
– –
+
+
–
–
+
+
–
–
+
+
Содержание FUSION-TEC WR Series
Страница 2: ......
Страница 50: ......
Страница 53: ......
Страница 63: ......
Страница 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 75: ......
Страница 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Страница 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Страница 96: ......
Страница 100: ......