Manual 2100-643C
Page
51 of 59
Screen
Menu Item
Range
Default Value
Description
Language
Language
0-1
English
Probe Adjustment
Analog Inputs
SAT Input B001
Offset
-9.9 – 9.9
0
Value
-3276.8 –
3276.7
OAT Input B002
Offset
-9.9 – 9.9
0
Value
-3276.8 –
3276.7
RAT Input B003
Offset
-9.9 – 9.9
0
Value
-3276.8 –
3276.7
Outdoor Air Humidity
Input B005
Offset
-9.9 – 9.9
0
Value
-3276.8 –
3276.7
Freezestat Input B007
Offset
-9.9 – 9.9
0
Value
-3276.8 –
3276.7
Manual Management
Analog Inputs
Supply Air Temp
Manual Control B001
Off/On
Off
On to manually change temperature seen
by controller
Manual Position
-1000 – 1000
0
Degrees of change in sensor for manual
control
Value
(Temp + Value)
Current temperature plus the value in
manual position
Outdoor Air Temp
Manual Control B002
Off/On
Off
On to manually change temperature seen
by controller
Manual Position
-1000 – 1000
0
Degrees of change in sensor for manual
control
Value
(Temp + Value)
Current temperature plus the value in
manual position