![Bard D25A2PA Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/bard/d25a2pa/d25a2pa_installation-and-service-instructions-manual_3947242059.webp)
Manual 2100-643C
Page
59 of 59
Screen
Menu Item
Range
Default Value
Description
Cooling Stage 2
Enable
No/Yes
Yes
Channel
3
Direction
N.O./N.C.
N.O.
Status
Off
Heating
Enable
No/Yes
Yes
Channel
4
Direction
N.O./N.C.
N.O.
Status
Off
Blower
Enable
No/Yes
Yes
Channel
7
Direction
N.O./N.C.
N.O.
Status
Off
Analog Outputs
Blower Motor
Enable
Yes/No
Yes
Channel
1/0
1
Action
Direct/Reverse
Direct
Minimum
0 – 10v
0v
Maximum
0 – 10v
10v
Damper
Enable
Yes/No
Yes
Channel
2/0
2
Action
Direct/Reverse
Direct
Minimum
0 – 10v
2.7v
Maximum
0 – 10v
10v
Factory Settings
Damper Delay Test
Enable
Yes/No
Yes
Voltage
0 – 10v
2.5v
Time
0s – 999s
30 seconds
Blower Status Switch
Minimum Off
0s – 999s
45 seconds
Unit Controller
Serial Number
00000000000000
Wall-mount unit serial number
Model Number
60 X
Wall-mount unit model number
End of FACTORY