Manual 2100-643C
Page
47 of 59
Screen
Menu Item
Range
Default Value
Description
Reset Temperature
0°F – 99.9°F
55°F
Temperature sensed by Freezestat which
cancels compressor shutdown
Reset Time
0-999
300 seconds
Time alloted which will also cancel
compressor shutdown
Blower Settings
Continuous
None/Both/Lead
None
Blower Speeds
Heat
0.0 – 7.6V
7.0V
Control voltage supplied from wall-mount
unit control boards to blower in heat
Econ
0.0 – 7.6V
7.0V
Control voltage supplied from wall-mount
unit control boards to blower in regular
DC free cooling
Econ Low Temp
0.0 – 7.6V
3.8V
Control voltage supplied from wall-mount
unit control boards to blower in low
ambient condition DC free cooling
Full Load
0.0 – 7.6V
6.3V
Control voltage supplied from wall-
mount unit control boards to blower in
mechanical cooling
Low Pressure Setup
Outside Setpoint
0°F – 99.9°F
55°F
Temperature at which control separates
two (2) different low pressure situations
Differential
0°F – 9.9°F
5°F
This differential applies to the outside
setpoint
Above Setpoint Delay
0-999
120 seconds
Any low pressure situation above the
outside setpoint will be delayed 120
seconds before an alarm is initialized
Below Setpoint Delay
0-999
180 seconds
Any low pressure situation below the
outside setpoint will be delayed 180
seconds before an alarm is initialized
Time btwn 2 1p
0-999
15 minutes
Fieldbus Address
0-999
11
Compressor Timers
Minimum Off
0-999
120 seconds
Once stopped, the compressor remains
inactive for this period of time
Minimum On
0-999
300 seconds
Once started, the compressor remains on
for this period of time
Comp Stage Delay
0-999
60 seconds
Minimum run time for first stage of two-
stage compressors
Modulating Setup
Damper
DIR/REV Both
Cntrl: DIR P+1
P/P+I/PID
Band
0-999
75
Deadband
99.9
0
Int.
0-999
120 seconds
Minimum
0-999
0