WALL-MOUNT UNIT ARCHITECTURE
CAUTION:
The Bard DC Free Cooling Unit System has been pre-programmed with what is widely considered to
be the best settings for efficiency and operation. Any changes to internal programming through the LC Series
controller or the TEC-EYE
TM
not covered within this manual may cause the systems to operate improperly, cause
internal damage to the HVAC units, cause the shelter to overheat or other very serious consequences. Although
complete controller programming architecture for the wall-mount unit controller has been provided, going outside the
boundaries of what has been covered in this manual not recommended.
Screen
Menu Item
Range
Default Value
Description
MAIN STATUS SCREEN
The Status screen is the default screen on startup, and anytime more than 5
minutes has elapsed from last change. (Use UP/DOWN keys to scroll)
Displays current data
RAT
°F
Current return air temperature
SAT
°F
Current supply Air temperature
OAT
°F
Current outdoor air temperature
OAH
%
Current outdoor air humidity
Dewpoint
°F
Current temperature of dewpoint
Blower
Off/On
Displays status of blower
Damper
%
Displays percentage of current opening
Master Control
Master Control
Current operational status, "Running
Stand Alone" if communication lost
Status
Unit On
D-Series controller board is currently
active, "Off by Keyboard" if disabled by
TEC-EYE
TM
MAIN MENU
Main Menu screen(s) allows access to operational programming, access by pressing MENU key at any time. (MENU key
to enter, use UP/DOWN keys to scroll)
ON/OFF UNIT
Unit Address
1
Physical address of controller
Power by Display
On/Off
On
Status
Blower
"OFF by Keyboard" system has been
turned off at controller
End of ON/OFF UNIT
SETPOINTS
All setpoint changes are limited to 60 minutes
Cooling Setpoint
65°F – 90°F
77°F
Heating Setpoint
52°F – 75°F
60°F
Cooling Stg. Diff.
1°F – 5°F
5°F
Heating Stg. Diff.
1°F – 5°F
2°F
FreeCool
55°F, 57°F,
59°F, 61°F
55°F
DC OA-Return Diff.
0°F – 99.9°F
7°F
Supply Temp Low Limit
28°F – 65°F
35°F
Differential
0°F – 99.9°F
20°F
Damper Time
0-999
150 seconds
Time alloted before damper fail is
realized
Runtest Time
0-999
60 seconds
Freeze Temp Low Limit
0°F – 99.9°F
30°F
Temperature sensed by Freezestat which
initiates compressor shutdown