FIGURE 2.18
VDC Polarity Check
Bard System
Supply Breakers
Shelter VDC Power Supply
-48VDC, Positive Ground
+
If the VDC wiring is not terminated correctly on the specific polarity-indicated terminals of the VDC terminal
block, the VDC controls and motors will not activate and the wall-mounted unit will not function.
Step 1
Multimeter set to VDC:
Display reveals "0" voltage potential
Bard System Supply Breakers:
VDC breaker in OFF position
Shelter VDC Power Supply
-48VDC, Positive Ground
0 VDC
Bard System Supply Breakers:
VDC breaker in OFF position
Step 2
Multimeter set to VDC:
Positive-to-ground reveals
"0" voltage potential
Shelter VDC Power Supply
-48VDC, Positive Ground
0 VDC
Step 3
Multimeter set to VDC:
Negative-to-ground reveals
"-48" voltage potential
Bard System Supply Breakers:
VDC breaker in OFF position
Shelter VDC Power Supply
-48VDC, Positive Ground
-48 VDC