Installation • Installation
138
Power Panel 500 user's manual V1.40
1.5 Spacing for air circulation
In order to guarantee sufficient air circulation, allow the specified amount of space above, below, to the side and
behind the Power Panel 500. The minimum specified spacing is indicated in the following diagram. This applies
to all Power Panel 500 variants.
At least
40 mm spacing
At least
40 mm spacing
Figure 66: Spacing for air circulation - Front view
At least
80 mm spacing
Ai
r out
let
At
least
80
m
m
spaci
ng
Ai
r i
nt
ake
At
least
80
m
m
spaci
ng
Figure 67: Spacing for air circulation - Side view
Information:
The spacing specifications for air circulation are based on the worst-case scenario for operation at the
maximum specified ambient temperature (see "Temperature specifications" in the chapter "Technical
data").
If the spacing specifications for air circulation cannot be adhered to, then the maximum specified tem-
peratures for the temperature sensors (see "Temperature sensor locations" in the chapter "Technical
data") must be monitored by the user and appropriate measures taken if they are exceeded.