ANOMALY
The burner goes to shut down
spraying liquid fuel but without fla
-
me presence. (Red light on).
The burner goes into “lock-out”,
gas flows, but there is no flame
(red light on).
Noisy burner pump.
POSSIBLE CAUSE
1
Pump pressure is not regular.
2
Water in the fuel.
3
Too much combustion air.
4
Air passage between deflector disk
and diffuser excessively closed.
5
Nozzle worn out or dirty.
1
Air - gas ratio incorrect.
2
Gas pipe has not been properly
bled of air at the first ignition.
3
The gas pressure is insufficient or
excessive.
4
Air passage between deflector disk
and diffuser too closed.
1
Pipe diameter too small.
2
Air infiltration in the pipes.
3
Dirty fuel filter.
4
Excessive distance and/or differen-
ce in level between the tank and
the burner or numerous accidental
leakages (elbows, curves, bottle-
necks, etc.)
5
Deteriorated flexible pipes.
REMEDY
1 Adjust.
2
Drain water from the tank using a
suitable pump. Never use the burner
pump for this purpose.
3
Reduce combustion air.
4
Correct the position of the combustion
head adjusting device.
5
Clean or replace.
1
Correct the air - gas ratio.
2
Bleed the gas pipe again, with due
caution.
3
Check the maximum gas pressure va-
lue at the time of ignition (use a water
pressure gauge, if possible).
4
Adjust the deflector disk - diffuser.
1
Replace it according to the in-
structions.
2
Check and eliminate infiltrations.
3
Remove and wash.
4
Adjust the length of the suction pipe to
reduce the distance.
5 Replace.
Содержание TBML 50MC
Страница 2: ......
Страница 43: ...ITALIANO 41 44 0006160003_201510 SCHEMI ELETTRICI ...
Страница 44: ...ITALIANO 42 44 0006160003_201510 ...
Страница 45: ...ITALIANO 43 44 0006160003_201510 ...
Страница 87: ...ENGLISH 41 44 0006160003_201510 WIRING DIAGRAMS ...
Страница 88: ...ENGLISH 42 44 0006160003_201510 ...
Страница 89: ...ENGLISH 43 44 0006160003_201510 ...
Страница 91: ......