ENGLISH
21 / 44
0006160003_201510
•
When the burner is operating in the 1st stage, adjust the amount
of air necessary to ensure an efficient combustion, see “AIR
ADJUSTMENT ON THE BURNER HEAD” and 0002937920 for
the diesel 1st stage cam adjustment.
•
After adjusting the 1st stage air the burner stops disconnecting
the current from the main switch, the electric circuit comman-
ding the second stage activation closes connecting the 4-pole
connector according to the wiring diagram.
• Adjust the quantity of air necessary for the maximum flow rate
(2nd stage) through the screw/s at the bearing -12.
-
clockwise rotation: the air flow increases
-
in an anti-clockwise direction the air flow decreases
•
Now the equipment is activated again and moves to the second
stage automatically, according to the program set by the pro-
grammer.
acc_reg001.psd
img 010.jpg
12
13