ENGLISH
56 / 62
0006081528_201711
BLOCK DIAGRAM ILLUSTRATING THE PRINCIPLE OF L.P.G. PRESSURE REDUCTION IN TWO STAGES FOR BURNER OR BOILER
Pressure gauge and pressure
intake
LPG tank
1st step reducer
Output ~ 1.5 bar
Flow rate ~ double the maximum required by the
user
2nd step reducer
Output ~ 30 hPa (mbar)
Flow rate ~ double the maximum required by
the user
Y filter
Filter
Filter
Pressure intake
2nd step reducer
Output ~ 30 hPa (mbar)
Flow rate ~ double the maximum required by
the user
Y filter
Ball cock
Vibration-proof
joint
Burner
Free-standing or wall-mounted
boiler
Pipe fitting
SUPPLIED BY THE MANUFACTURER
TO BE CARRIED OUT BY THE INSTALLER