DESCRIPTION OF THE TWO-STAGE
PROGRESSIVE OPERATION
Blown air burners with electronic modulation may be used on hearths
under strong pressure or in a vacuum, according to the corresponding
operating curves.
They combine a very stable flame with total safety and high
performance.
The burner is fitted with an electronic cam controlled by a
microprocessor for intermittent operation, and for the control and
monitoring of the blown air gas burners. Electronic modulation
achieved by means of two step air gas regulation motors.
The burner is fitted with a valve tightness control device. To better
understand the operation of the electronic cam, read the specific
instructions in the manual provided carefully.
The term two-stage progressive operation indicates that transition
from the first to the second state (from minimum to maximum
operation) is progressive in terms of both amount of combustion air
let in and the amount of output fuel. This results in a greater pressure
stability in the gas supply network.
The variation range of flow rate is approximately 1 to 1/3.
Ignition is preceded by the combustion chamber pre-ventilation, as
set forth by the standards, with air open and with a duration of approx.
30 seconds.
If the air pressure switch has detected a sufficient pressure, the
ignition transformer activates at the end of the ventilation phase and
after 3 seconds the safety and main valves open in sequence.
Gas reaches the combustion head, mixes with air supplied by the fan
and is ignited. The gas supply is regulated by the butterfly gas valve.
Three seconds after the valves (main and safety) come on, the ignition
transformer goes off. Thus the burner is ignited at the ignition point.
Thus the burner is ignited at the ignition point.
The presence of the flame is detected by the control device (ionisation
probe immersed in the flame).
The programmer relay moves past the locking position and sends
voltage to the air/gas supply adjustment servomotors, which go to the
minimum point (200).
If the second stage boiler thermostat (or pressure switch) allows it (set
to a temperature or pressure value higher than the existing value in
the boiler), the air/gas supply servomotors will start to turn, gradually
increasing gas and combustion air supplies up to the maximum
supply to which the burner has been set (999).
CAUTION / WARNINGS
The electronic cam controls the burner, activating the
combustion air, gas servomotor and the fan motor, if the
inverter is fitted, according to a curve that has ten points set
(see curve regulation table).
The burner remains in the maximum output position as long as the
temperature or pressure reaches a value sufficient enough to cause
the intervention of the probe that rotates the gas/air flow rate regulation
servomotors. This progressively reduces the gas, combustion air and
motor's RPM (if the inverter is fitted) to the minimum.
If the threshold value (temperature or pressure), to which the complete
shut-down device (thermostat or pressure switch) is set, is reached
even with minimum gas and air output, the burner will be shut down
when the device is triggered.
As the temperature or pressure drops below the shut-down device's
(thermostat or pressure switch) set point, the burner will be turned on
again as described above.
• During regular operation the second stage boiler thermostat
(or pressure switch) applied to the boiler detects variations
in demand and automatically adapts fuel and combustion air
supplies, increasing or decreasing the rotation of the air/gas supply
servomotors.
• This causes the air/gas output control system to balance the
amount of heat supplied to the boiler with the amount it gives off
during use.
•
If a flame does not appear within three seconds from the opening
of the gas valves, the control equipment will lock out (shutting
down the boiler completely and showing the corresponding error
message on the display (3)).
• To "unlock" the equipment, press the RESET button (4) for about
half a second.
Содержание btg 20 me
Страница 2: ......
Страница 29: ...ITALIANO 29 32 0006081528_201711 SCHEMI ELETTRICI...
Страница 30: ...ITALIANO 30 32 0006081528_201711...
Страница 31: ...ITALIANO 31 32 0006081528_201711...
Страница 59: ...ENGLISH 59 62 0006081528_201711 WIRING DIAGRAMS...
Страница 60: ...ENGLISH 60 62 0006081528_201711...
Страница 61: ...ENGLISH 61 62 0006081528_201711...
Страница 63: ......