ENGLISH
57 / 62
0006081528_201711
INSTALLATION LAYOUT WITH VAPORISER
3
2
1
4
Vaporizzatore
A
C
B
D
A Any emergency gas phase connection
B Vaporiser
C Tank
D 1st stage reducer unit
Warnings
• The vaporiser is considered a dangerous point and should therefore
be situated at a safe distance from any building.
•
The electrical system must be AD-EP (anti-deflagration-explosion
proof).
• The L.P.G. pipelines must be made of SS steel with welded or
flanged joints NP 40 (nominal pressure 40 bar). Threaded joints are
prohibited.
Specific materials
• Liquid recovery valve
•
Liquid delivery cock with flow limiter.
•
Steel fitting with welded tang and copper washer.
• 18-bar safety valve with welded steel coupling.