OPERATING RANGE
BTG 20ME
BTG 28ME
BTG 15ME
IMPORTANT
The operating ranges are obtained from test boilers corresponding to Standard EN676 and are indicative of the burner-boiler combination.
For correct working of the burner, the size of the combustion chamber must correspond to current regulations; if not the manufacturers
must be consulted.
The burner shall not operate outside its specific operating range.
¹) NATURAL GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh natural
gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE GAS EMISSIONS
Propane / natural gas CO emissions ≤ 100 mg/kWh
Class
NOx emissions in mg/kWh propane
gas
1
≤ 230
2
≤ 180
3
≤ 140