6.14 Examples (stroke counters)
6.14.1 Parameterizing a stroke counter via ISDU
The following must be set individually:
– Position value (PW) for stroke counter 1 to 1000 μm:
0x2710
– Set span (SP) for stroke counter 1 to 1000 μm: 0x03E8
– Set stroke counter 1 mode to active: 0x01
Command sequence:
Index
Subindex
Value
Description
0x020E
0x01
0x2710 Set PW stroke counter
1 to 10000 μm
0x020E
0x02
0x03E8 Set SP stroke counter
1 to 1000 μm
0x020E
0x03
0x01
Set stroke counter 1
mode to enabled
Tab. 6-18: Command sequence
The above configuration can also be written completely as
a parameter set.
In this case all values are sent to Subindex 0.
Index
Subindex
Value
Description
0x020E
0x00
0x2710
0x03E8
0x01
Set PW stroke counter
1 to 10000 μm; set SP
stroke counter 1 to
1000 μm; set stroke
counter 1 mode to
disabled
Tab. 6-19: Send values to Subindex 0
6.14.2 Move target to stroke counter position value
and save – system command
The position value of stroke counter range 2 should be set
per target to position 2000 μm.
Index
Subindex
Value
Description
0x020D
0x00
0x02
Select stroke counter
channel 2
Move target to 2000μm
0x0002
0x00
0xB6
Teach stroke counter
position
Tab. 6-20: Set position value of stroke counter range 2 per target to
2000 μm
Set the span (SP) and mode for stroke
counter 2 also using parameterization via
ISDU.
Configure stroke counter 2 corresponding to Tab. 6-16.
6.14.3 Reset stroke counter configuration to default
values – system command
Reset the configuration of stroke counter 3 to the default
values:
Index
Subindex
Value
Description
0x020D
0x00
0x03
Select stroke counter
channel 3
0x0002
0x00
0xB7
Reset stroke counter
configuration
Tab. 6-21: Reset stroke counter 3 to the default values
6
IO-Link interface (continued)
www.balluff.com
25
english
BIP LD2-T017-01-EP _ _ / EP _ _ -S4
Inductive Positioning System
Содержание BIP LD2-T017-01-EP-S4 Series
Страница 2: ...www balluff com...
Страница 3: ...BIP LD2 T017 01 EP_ _ BIP LD2 T017 01 EP_ _ S4 Betriebsanleitung deutsch...
Страница 4: ...www balluff com...
Страница 32: ......
Страница 33: ...BIP LD2 T017 01 EP_ _ BIP LD2 T017 01 EP_ _ S4 User s Guide english...
Страница 34: ...www balluff com...
Страница 62: ......
Страница 63: ...BIP LD2 T017 01 EP_ _ BIP LD2 T017 01 EP_ _ S4 Notice d utilisation fran ais...
Страница 64: ...www balluff com...
Страница 92: ......
Страница 93: ...BIP LD2 T017 01 EP_ _ BIP LD2 T017 01 EP_ _ S4 Manuale d uso italiano...
Страница 94: ...www balluff com...
Страница 122: ......
Страница 123: ...BIP LD2 T017 01 EP_ _ BIP LD2 T017 01 EP_ _ S4 Manual de instrucciones espa ol...
Страница 124: ...www balluff com...
Страница 152: ......
Страница 153: ...BIP LD2 T017 01 EP_ _ BIP LD2 T017 01 EP_ _ S4...
Страница 154: ...www balluff com...
Страница 157: ...2 1 BIP IO Link PLC IO Link BIP 2 2 BIP BIP 2 3 2 4 2 www balluff com 5 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 158: ...3 1 3 1 35 25 4 1 15 1 25 31 20 3 5 4 3 2 LED 3 2 BIP IO Link 3 6 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 160: ...4 4 2 4 4 1 2 4 S4 BIP 1 L 18 30 V 2 1 3 L GND 4 C Q 1 4 1 4 3 BIP BIP BIP BIP 20 m 8 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 161: ...5 1 BIP 1 2 3 BIP BIP 5 2 BIP BIP 5 www balluff com 9 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 174: ...6 11 6 11 1 PW SP Custom Operating Total Operating 6 6 3 1 1 2 3 2 3 2 1 6 IO Link 22 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 182: ......
Страница 183: ...BIP LD2 T017 01 EP_ _ BIP LD2 T017 01 EP_ _ S4...
Страница 184: ...www balluff com...
Страница 187: ...2 1 IO Link BIP PLC IO Link BIP 2 2 BIP BIP 2 3 2 4 2 www balluff com 5 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 188: ...3 1 3 1 35 25 4 1 15 1 25 31 20 3 5 4 3 2 LED 3 2 BIP IO Link 3 6 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 191: ...5 1 BIP 1 2 3 BIP BIP 5 2 BIP BIP 5 www balluff com 9 BIP LD2 T017 01 EP_ _ EP_ _ S4...
Страница 204: ...6 11 6 11 1 PW SP 3 2 Custom Operating Total Operating 6 6 3 1 1 2 3 2 3 2 1 6 IO Link 22 BIP LD2 T017 01 EP_ _ EP_ _ S4...