Care2
Installation Instructions
16
Care2 issue 7
2.3 I
NSTALLING
C2CFPE I
NTERFACE
C
ARD
As supplied the Care2 system is permanently active and all DRS
Refuge Remotes are able to make calls all the time.
The C2CFPE Fire Panel Interface card enables the DRS Refuge
Remotes to be active only when a Fire Panel is active.
The Interface Card also provides the Common Fault Volt Free
contacts and the Ethernet contacts.
Figure 2.10 — Typical C2CFPE Expansion Line Card
1. Ensure the Mains 230V supply is isolated.
2. Remove the 4 off M3x10 screws securing the front door of
the Console.
Figure 2.11 — Remove 4 x Front Panel Screws
3. Carefully open the hinged door.
4. Disconnect and isolate the battery backup supply.
5. Fit the C2CFPE unit to the left of the first line card using the
M4x8 screws provided.
!
W
ARNING
Before attempting to fit this component, ensure the Mains Power
Supply and Battery Backup have been disconnected as described
in the following procedure.