4-4 Troubleshooting
Indication
Possible Cause
Corrective Action
MIN. Output Frequency
Limit set too high
Adjust setting of Min. Output
Frequency Limit
Motor will
not stop
Improper speed command
Verify control is receiving proper
command signals at the control
terminal strip
not stop
rotation
Verify control is set to receive your
type of speed command
Speed potentiometer
failure
Replace potentiometer
Oscillating load
Correct the loading problem
Unstable
Unstable input power
Correct the input power problem
Unstable
motor speed
Slip compensation set too
high
Adjust slip compensation
Torque boost set too high
Adjust torque boost setting
Motor runs
rough at low
Misalignment of
motor/load coupling
Verify and align motor/load
coupling
speeds
Defective motor
Replace motor.
Clean the motor air intake and
exhaust areas
Insufficient motor
ventilation
Check external blower for proper
operation
ventilation
Verify motor’s internal fan is
securely coupled to shaft
Check for excessive motor load
External trip
fault
Motor drawing excessive
current
Verify proper motor and control
rating
Adjust V/Hz profile
Volts/Hertz ratio not
Adjust control base frequency
adjusted
Adjust Max. Output Volts
Connect thermostat
No thermostat connected
Verify connection of all external trip
circuits used with thermostat
Over current
Accel/Decel rate set too
quickly
Increase Accel/Decel rate
Over current
Torque boost set too high
Reduce torque boost setting
Timed
overload
Motor overloaded
Verify proper motor and control
rating
overload
fault
Correct the loading problem
Содержание ID10101-E
Страница 1: ...Series 10 Inverter Control Installation and Operating Manual 2 00 MN710 AC INVERTER ...
Страница 13: ...1 8 General Information ...
Страница 35: ...2 22 Installation ...
Страница 67: ...4 6 Troubleshooting ...
Страница 68: ...Section 5 Illustrations Illustrations 5 1 ...
Страница 69: ...5 2 Illustrations ...
Страница 70: ...Illustrations 5 3 3 5 HP NEMA 1 230 460VAC ...
Страница 71: ...5 4 Illustrations ...