Installation 2-19
Jumper J19 - Used to select the active state of the opto isolated
inputs (Pull-Up or Pull-down Logic) and to select the type of
analog speed command signal to be applied. The available
analog speed command signals are 0-5 VDC, 0-10 VDC, 0-20
mA, and 4-20 mA. A 5kohm 1/2 Watt Potentiometer can be used
by configuring for 0-5 VDC.
21-Operating Mode - Defines the source for speed reference
command and RUN/STOP control inputs.
24-Analog Command Select - Defines the type of external
speed reference command and if the command is accepted as a
direct command or inverted command.
41-Accel/Decel/Coast Select - Selects which Accel and Decel
Time parameters are applied to the control output and also
defines if Coast to Stop is active after a STOP command.
77-External Trip Select - Defines if a normally open or normally
closed contact at control terminal MOL will generate an External
Trip Fault (F07) or a Coast to Stop condition.
82-Start Options - Sets the operation of Auto Restart and
Synchro Starts. Also enables or disables the STOP key as an
E-Stop when operating from the control terminal strip and the
Stop function due to a disconnection of an external command
line connected at the control terminal strip.
Содержание ID10101-E
Страница 1: ...Series 10 Inverter Control Installation and Operating Manual 2 00 MN710 AC INVERTER ...
Страница 13: ...1 8 General Information ...
Страница 35: ...2 22 Installation ...
Страница 67: ...4 6 Troubleshooting ...
Страница 68: ...Section 5 Illustrations Illustrations 5 1 ...
Страница 69: ...5 2 Illustrations ...
Страница 70: ...Illustrations 5 3 3 5 HP NEMA 1 230 460VAC ...
Страница 71: ...5 4 Illustrations ...