Operation 3-9
Electronic Pot Control Terminal Logic
Parameter 21-Operating Mode = 6 or 7
COMMAND
CONTROL TERMINALS
DESCRIPTION
FWD
REV
PS1
PS2
STOP
OPEN
OPEN
X
X
Speed = 0
CLOSED
CLOSED
X
X
FWD Decrease
CLOSED
OPEN
CLOSED
X
FWD Hold
CLOSED
OPEN
OPEN
OPEN
FWD Increase
CLOSED
OPEN
OPEN
CLOSED
REV Decrease
OPEN
CLOSED
CLOSED
X
REV Hold
OPEN
CLOSED
OPEN
OPEN
REV Increase
OPEN
CLOSED
OPEN
CLOSED
X=Don’t Care Condition.
31-Min Output Frequency - Sets a minimum output frequency
provided to the motor. During operation the output frequency will
not be allowed to go below the minimum output frequency unless
the motor is starting from 0 Hz or is ramped to a stop. The
available values are 0 to 400 Hz. The factory setting is 0 Hz.
32-Max Output Frequency - Sets a maximum output frequency
provided to the motor. The available values are 20 to 400 Hz.
The factory setting is 60 Hz.
42-Accel Time #1 - Sets the time in seconds for the output
frequency of the inverter to linearly increase from 0 Hz to the
frequency specified by parameter 32-Max Output Frequency.
The adjustable range is from 0 Sec to 600 Sec.
43-Decel Time #1 - Sets the time in seconds for the output
frequency of the inverter to linearly decrease from the frequency
specified by parameter 32-Max Output Frequency to 0 Hz. The
adjustable range is from 0 Sec to 600 Sec.
Содержание ID10101-E
Страница 1: ...Series 10 Inverter Control Installation and Operating Manual 2 00 MN710 AC INVERTER ...
Страница 13: ...1 8 General Information ...
Страница 35: ...2 22 Installation ...
Страница 67: ...4 6 Troubleshooting ...
Страница 68: ...Section 5 Illustrations Illustrations 5 1 ...
Страница 69: ...5 2 Illustrations ...
Страница 70: ...Illustrations 5 3 3 5 HP NEMA 1 230 460VAC ...
Страница 71: ...5 4 Illustrations ...