© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
30 |
=
BHGE
Dismantling the SVI II AP from Rotary Valves
Before carrying out any work on the device, power off the instrument or ensure that the device’s
location conditions for potentially explosive atmosphere permit the safe opening of the cover.
To remove the SVI II AP Controller from a rotary valve perform Steps 1 - 9 on page
27 in reverse.
Mounting the SVI II AP on Reciprocating Valves
The process of mounting the SVI II AP on a reciprocating valve consists of mounting the unit on
the actuator that is attached to the valve. This section describes the procedure for mounting the
SVI II AP on Reciprocating Valves (using Masoneilan’s 87
⁄
88 Multi-Spring actuators as an exam-
ple).
Mounting the SVI II AP on a Reciprocating Actuator
Tools required:
7
⁄
16" Combination Wrench (2 required)
3
⁄
8" Combination Wrench
1
⁄
2" Combination Wrench
Phillips Head Screw Driver
5 mm Hex Key Wrench
1. Ensure that the lever is pinned to the magnet assembly and held securely by an
M5 flat head screw to ensure that the magnet axis is vertical when the lever is in
the valve closed position. Tighten the lever screw securely. Refer to Figure 14.
Figure 14
Magnet Holder for Reciprocating Valves
M5 Flat
Pin
head screw
Содержание Masoneilan SVI II AP
Страница 6: ...This page intentionally left blank...
Страница 10: ...This page intentionally left blank...
Страница 68: ...This page intentionally left blank...
Страница 90: ...2018 Baker Hughes a GE company LLC All rights reserved 90 BHGE Spare Parts...
Страница 92: ...2018 Baker Hughes a GE company LLC All rights reserved 92 BHGE...
Страница 94: ...This page intentionally left blank...
Страница 102: ...This page intentionally left blank...
Страница 105: ...This page intentionally left blank...
Страница 106: ...This page intentionally left blank...
Страница 107: ...This page intentionally left blank...