Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
19
Pushbutton Locks and Configuration-Lock Jumper
Before performing any of these functions with the local display you must first ensure that the
pushbuttons are placed in the unlocked mode using ValVue. The positioner is provided in the un-
locked mode. See ValVue documentation for more details.
The SVI II AP offers several levels of accessibility. It may be desirable, after initial setup, to lock the
pushbuttons so that the SVI II AP parameters cannot be inadvertently changed by the buttons.
Several levels of pushbutton locks are provided.
Table 2: Pushbutton Lock Security Level
Level
Access
Security Level 3
Allow Local Buttons: Buttons on the SVI II AP are fully enabled.
Security Level 2
Lock Out Local Calibration and Configuration: Use the buttons to per-
form operations in normal operating mode and manual mode. Do not
go to configure or calibrate mode.
Security Level 1
Lock Out Local Manual: Examine variables in normal operating mode
but do not put the valve in manual operating mode. Access to cali-
brate or configure modes is not available.
Security Level 0
Lock Out All Buttons: The buttons are disabled (level 0).
Содержание Masoneilan SVI II AP
Страница 6: ...This page intentionally left blank...
Страница 10: ...This page intentionally left blank...
Страница 68: ...This page intentionally left blank...
Страница 90: ...2018 Baker Hughes a GE company LLC All rights reserved 90 BHGE Spare Parts...
Страница 92: ...2018 Baker Hughes a GE company LLC All rights reserved 92 BHGE...
Страница 94: ...This page intentionally left blank...
Страница 102: ...This page intentionally left blank...
Страница 105: ...This page intentionally left blank...
Страница 106: ...This page intentionally left blank...
Страница 107: ...This page intentionally left blank...