Troubleshooting
84
Electrical Control System
2.4.4.8. E6 malfunction (Only for 36K, 48K with 1 phase)
E6 display
PFC module protection
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Measure whether the
voltage between P and N is
normal refer to the
Appendix
3
?
No
Check
whether
the
inductance of PFC module
is good? If the inductance is
good, the resistance of the
two ports is 0
Yes
Replace the inductance
No
Connect it tightly, check
normal or not
Replace the outdoor main board
Yes
Yes
No
No
Replace the PFC module
Trouble is solved