Electrical Control Function
Electrical Control System
57
1.3.2.4 Evaporator low temperature T2 protection.
When T2<2
℃
and lasts for 3 minutes, the indoor has no capacity demand and resume till T2
≥
7
℃
.
1.3.2.5 Condenser high temperature T3 protection
When T3≥65
℃
for 3 seconds, the compressor will shut off. When T3
<
52,the compressor will restart.
1.3.3 Heating Mode
1.3.2.1 Outdoor PMW open angle control
The unit is working in heating mode with the EXV open 300P for 3 minutes, then adjusting PMW open
angle according to the temperature of compressor discharge every 2 minutes.
1.3.3.2 Outdoor fan running rules:
T2
On
30~36K
T3
Resume
Off
Decrease
Hold