Electrical Control Function
Electrical Control System
61
For 18-36K(1-Phase) models:
Condition of defrosting:
T3
≤
TempEnterDefrost_ADD
℃
and lasts for 40 minutes.
Defrosting action
:
4-Way valve
Indoor fan
Outdoor fan
480P
PMV
PMV running
6 mins with 300P
Compressor
10S
30S
TimeA
10S
no longer than 10min
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating
mode.
①
T3 >
TempQuitDefrost_ADD
℃
;
②
The defrosting time achieves 10min.
For 48K(1-Phase)
、
36-60K(3-Phase) models:
Condition of defrosting: