![Bailey platinum standard PTSP Series Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/bailey/platinum-standard-ptsp-series/platinum-standard-ptsp-series_product-instruction_467168019.webp)
INTRODUCTION
OPTIONS AND ACCESSORIES
1 - 10
WBPEEUI110506A0
Type PTSPA Absolute Pressure Transmitter Specifications
Table
lists the specifications unique to the Type PTSPA
absolute pressure transmitter.
OPTIONS AND ACCESSORIES
Table
lists the options and accessories available with the
Type PTSP pressure transmitter.
Reference accuracy - per
IEC 770 and SAMA
PMC 31.1
The reference accuracy includes the effects of linearity, hysteresis, repeatability,
and deadband. These values are for transmitters with zero based spans, silicone
oil fill, and Hastelloy C-276 isolating diaphragms at a reference temperature of
25°C (77°F). The value listed may vary depending on the URL and calibrated
span of the particular transmitter.
PTSPGF
±0.20% of span or ±
(% of span), whichever is greater
PTSPGG and PTSPGJ
±0.10% of span or ±
(% of span), whichever is greater
Pressure limits
The minimum sustained absolute pressure is 3.4 kPa (0.5 psi). The maximum
overpressure is listed in the following table.
Overpressure effect
This value is for transmitters with zero based spans, silicone oil fill, and Hastelloy
C-276 isolating diaphragms at a reference temperature of 25°C (77°F).
±0.05% of URL for line pressures 1.5 times URL.
Ambient temperature
effect on zero and span
These values are for transmitters with zero based spans, silicone oil fill, and
Hastelloy C-276 isolating diaphragms. The effects listed are for a variation of
±25°C (±45°F) from a calibration done at a temperature between -30° and
+80°C (-22° and +176°F), as long as the variation does not take the transmitter
out of the temperature specifications listed in Table
.
PTSPGF
±(0.15% URL + 0.10% span)
PTSPGG and PTSPGJ
±(0.08% URL + 0.10% span)
Weight
1.3 kg (2.9 lbs) without options or accessories.
NOTE:
1. Types PTSPGG and PTSPGJ pressure transmitters are not compensated for barometric pressure. Type PTSPGF pressure transmitters
are not linearized or thermally stabilized below atmospheric pressure.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
Table 1-5. Type PTSPG Gage Pressure Transmitter Specifications
(continued)
Property
Characteristic/Value
0.016
URL
×
Span
--------------------------------
0.008
URL
×
Span
--------------------------------
Type
URL
Overpressure Limit
(kPa)
(psi)
(kPa)
(psi)
PTSPGF
690
100
1,250
180
PTSPGG
3,000
450
6,000
870
PTSPGJ
40,000
5,800
41,368
6,000