DESCRIPTION AND OPERATION
FUNCTIONAL OPERATION
2 - 6
WBPEEUI110506A0
electronics housing. The cell temperature can be monitored on
the Type STT terminal.
Diagnostics
Continuous self-diagnostics are accessible on demand through
the Type STT terminal. Areas monitored include: cell; cell tem-
perature; electronics temperature; calibration; configured
pressure limits; input circuits; analog to digital converter;
microcontroller ROM, SEEPROM, EEPROM; and reference
voltages. Diagnostics identify the malfunctioning section of the
transmitter. The diagnostics may indicate if a calibration error
occurs.
Software Functions
Configuration and operational commands allow the input of an
ID tag for the transmitter configuration, selection of engineer-
ing units (primary and secondary), and definition of the out-
put. The output can be a linear representation of the input or a
function generator that follows a curve consisting of six
straight line segments. The output can be set for normal or
reverse acting and fixed to a specific value for plant startup
and troubleshooting purposes. Other commands allow the out-
put to be set to default values upon transmitter power up and
failure. The Type STT terminal also supports configuration,
input, output, and transmitter status monitoring. A damping
command is also available.