SECTION 8 - REPAIR AND REPLACEMENT PROCEDURES
INTRODUCTION
This section contains procedures for replacement of transmit-
ter components in the field.
The design of the Type PTSP pressure transmitter allows
replacement of components in as little as five minutes. All cali-
bration and configuration data are stored on both the amplifier
assembly and characterization board.
Replacement of the amplifier assembly requires no configura-
tion, as the characterization board automatically downloads
this information into the amplifier assembly. Replacement cell
and characterization board assemblies come with the standard
factory configuration (refer to Table
) and that data trans-
fers to the original amplifier assembly. If a configuration other
than the standard is required, the transmitter must go
through either a step-by-step configuration or must have a
configuration downloaded from the Type STT terminal as
described in
. In either case, calibrate the transmitter
according to the procedures in
.
COMPONENT REMOVAL AND INSTALLATION PROCEDURES
Use Figures
as visual aids when performing these
procedures.
All procedures assume replacement of the O-rings whenever a
component sealed by the O-ring is removed.
WARNING
Explosionproof/dust-ignitionproof installations and intrinsi-
cally safe installations in Class II or Class III hazardous loca-
tions require that the assembly be kept tight while circuits are
live unless the location is known to be nonhazardous at the
time.
System maintenance must be performed only by qualified per-
sonnel and only after securing equipment controlled by the cir-
cuit. Altering or removing components from an active circuit
may upset the process being controlled.
CAUTION
If the cell and characterization board assembly has been
cleaned for oxygen and chlorine service, do not compromise
the integrity of this cleaning during these procedures. Impuri-
ties will react with oxygen and chlorine and damage the trans-
mitter and the process.