![Bailey platinum standard PTSP Series Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/bailey/platinum-standard-ptsp-series/platinum-standard-ptsp-series_product-instruction_467168014.webp)
INTRODUCTION
NOMENCLATURE
WBPEEUI110506A0
1 - 5
NOMENCLATURE
The Type PTSP pressure transmitter has 15 nomenclature
positions. Positions five through 15 each have customer select-
able options. Use Table
to select or verify transmitter type.
Table 1-2. Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Platinum Standard Smart Pressure Transmitter
P Type Cell
P T S P _ _ _ _ _ _
_
_
_
_
_
Measurement application
A _ _ _ _ _
_
_
_
_
_ Absolute pressure
G _ _ _ _ _
_
_
_
_
_ Gage pressure
Measurement range
1
E _ _ _ _
_
_
_
_
_
F _ _ _ _
_
_
_
_
_
G _ _ _ _
_
_
_
_
_
G _ _ _ _
_
_
_
_
_
J _ _ _ _
_
_
_
_
_
Diaphragm material and fill fluid
1 _ _ _
_
_
_
_
_
2 _ _ _
_
_
_
_
_
A _ _ _
_
_
_
_
_
B _ _ _
_
_
_
_
_
E _ _ _
_
_
_
_
_
F _ _ _
_
_
_
_
_
Pressure connection material
1 _ _
_
_
_
_
_ Stainless steel 316 (ordered most)
A _ _
_
_
_
_
_ Hastelloy C-276
M _ _
_
_
_
_
_ For remote seal use (direct mount)
0 0
_
_
_
_
_
Not used - enter zeros
Nominal Range
Minimum Range
Types
kPa
psi
kPa
psi
0 - 200
0 - 30
0 - 5
0 - 0.8
PTSPA
0 - 690
0 - 100
0 - 69
0 - 10
PTSPG
0 - 3,000
0 - 450
0 - 75
0 - 11.3
PTSPA
0 - 3,000
0 - 450
0 - 200
0 - 30
PTSPG
0 - 40,000
0 - 5,800
0 - 1,000
0 - 145
All
Diaphragm Material
Fill Fluid
Types
Hastelloy C-276
Silicone oil
(ordered most)
All
Gold plated Hastelloy C-276 Silicone oil
Hastelloy C-276
Fluorinated oil
Gold plated Hastelloy C-276
Hastelloy C-276
Fluorinated oil - cleaned
for O
2
and Cl
2
service
Gold plated Hastelloy C-276
Содержание platinum standard PTSP Series
Страница 1: ......