INSTALLATION
SETUP AND PHYSICAL INSTALLATION
3 - 4
WBPEEUI110506A0
EZ CAL OPTION
1. The transmitter is delivered with a logo nameplate in place
of the EZ CAL option. Lift up on the logo nameplate to snap its
tab out of the EZ CAL option mounting hole.
2. Position the EZ CAL option on the top of the transmitter as
shown in Figure
and install the mounting screw.
Piping
Piping should be in accordance with ANSI Code B31.1 for pres-
sure piping.
The nameplate indicates the maximum allowable pressure. Do
not exceed this value when pressurizing the cell.
The piping between the primary element and the transmitter
must transfer the process pressure at the pipe taps to the
transmitter. Possible sources of error in this pressure transfer
are:
•
Leaks.
•
Friction loss, if continuous purging is used.
•
Trapped gas in a liquid line.
•
Trapped condensates in a gas line.
Figures
, and
show several installation examples.
These are typical piping arrangements only. They are intended
as generalized guides, and may not necessarily reflect the
exact configuration required for the particular service.
Wiring
There are two possible wiring configurations for the Type PTSP
pressure transmitter.
NOTE: Never connect the loop wiring to the test terminals.
WARNING
Consider the corrosive properties of the measured substance
when selecting piping materials. Degradation of the piping can
upset the process. Some process upsets can injure personnel
and damage equipment.
WARNING
When pressurizing, avoid overloading and pressure hammer.
Refer to the introduction section for the pressure limits of the
cell. Exceeding this pressure could result in damage to the cell
and cause serious injury to personnel.