INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-438A
2 - 3
Dipswitch Configuration
The dipswitches select the analog output type (voltage or cur-
rent) for the field device connected to the termination module.
Each channel is independent. Set the dipswitches for voltage or
current. Table
shows how to set dipswitches one through
eight (analog outputs one through eight respectively). Refer to
to find the dipswitch settings for the analog output
module.
Cabling Connections
The IAO termination module provides termination points for
the analog output module. Figure
shows the cable connec-
tion between the IAO termination module and the AOM mod-
ule. The cable can be either the NKTM01 Termination Module
Cable (ribbon cable), the NKTU02 Termination Module Cable
(PVC jacket) or the NKTU12 Termination Module Cable
(non-PVC jacket). Table
lists the IAO termination module
cable applications.
Table 2-1. NIAO01 Termination Module Dipswitch Settings
Application/
Signal Type
Dipswitch Position
Configuration
1
Binary Dipswitch
Configuration
Voltage
(1 - 5 VDC)
(0 - 10 VDC)
0111
Current
(4 - 20 mA)
1000
NOTES: 0 = OPEN or OFF, 1 = CLOSED or ON
1. 1 - 4 represent switch positions on dipswitches S1 - S8.
1
2
3
4
OPEN
1
2
3
4
OPEN
T00713A