INTRODUCTION
SPECIFICATIONS
1 - 4
I-E96-438A
®
Table 1-4. NIAO01 Termination Module Specifications
Property
Characteristic/Value
Surge Protection
Meets IEEE-472-1974 surge withstand capability test.
1
Wire Size:
Minimum
Maximum
Maximum wire size
when connecting three
wires to a single
terminal
22 gauge.
14 gauge.
One 16 gauge and two 18 gauge wires.
Mounting
Occupies one slot in a standard INFI 90 termination mounting unit.
Environmental:
Electromagnetic/
Radio Frequency
Interference
Ambient Temperature
Relative Humidity
Atmospheric Pressure
Air Quality
No values available at this time. Keep cabinet doors closed. Do not use
communication equipment closer than 2 meters from the cabinet.
0° to 70°C (32° to 158°F).
0% to 95% up to 55°C (131°F) noncondensing.
0% to 45% up to 70°C (158°F) noncondensing.
Sea level to 3 km (1.86 miles).
Bailey equipment should be operated and stored in a noncorrosive environment.
Cooling Requirements
No cooling is necessary when used in Bailey cabinets and operated within
stated environmental limits.
Certification
CSA certified for use as process control equipment in an ordinary
(nonhazardous) location.
NOTE: 1. Do not use the NKTM01 cable when compliance with IEEE-472-1974 is necessary.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.