Cable Installation
NKTM01 CABLE
This cable connects the IAO termination module to the AOM
module. The KTM cable is a flat ribbon cable. Do not bundle
the ribbon cable with other wiring. Bundling the cable can
cause cross talk in the ribbon cable. To install the cable:
NOTE: If the AOM module is installed, pull it several inches from the
backplane
before installing the cable.
1. Insert one end of the cable into the module mounting unit
backplane slot assigned to the AOM module. The cable should
latch securely in place. Card edge connector P3 of the AOM
module connects to this end of the cable.
Figure 2-2. Cable Connections
T00714A
P1
P3
P1
NKTM01
NKTU02/12
NIAO01
IMAOM01
Table 2-2. NIAO01 Termination Module Cable Applications
Nomenclature/
Description
Maximum Length
meters (feet)
Application
Connector
NKTM01 (ribbon cable)
30 (100)
Connects IAO
termination module to
AOM module
P1 on termination unit to
MMU backplane
NKTU02 (PVC)
61 (200)
NKTU12 (non-PVC)
61 (200)
CAUTION
Remove modules (slave, master or termination) from their
assigned slots before installing a cable to that slot.
ATTENTION
Retirer les modules (asservi, maître ou carte de raccordement)
de leur position assignée avant d'installer un câble à cette
position.