INSTALLATION
UNPACKING AND INSPECTION
2 - 2
I-E96-438A
®
UNPACKING AND INSPECTION
1. Examine the hardware immediately for shipping damage.
2. Notify the nearest Bailey Controls Company sales office of
any such damage.
3. File a claim for any damage with the transportation com-
pany that handled the shipment.
4. Use the original packing material and container to store the
hardware.
5. Store the hardware in an environment of good air quality,
free from temperature and moisture extremes.
SETUP/PHYSICAL INSTALLATION
This section explains how to configure and install the IAO ter-
mination module. The required procedures are fuse installa-
tion, dipswitch configuration, installing the termination
module, cable connection and termination wiring.
Fuse Installation
Two fuses should be installed with every IAO termination mod-
ule. Verify the fuses are installed in fuse clips F1 and F2 (see
Figure
for fuse clip locations). Fuse F1 is a 5.0 amp/ 250
volt fuse used for 24 VDC I/O power for the AOM module. Fuse
F2 is a 3.0 amp/250 volt fuse used for 24 VDC I/O power for
external devices.
Figure 2-1. NIAO01 Termination Module Layout
P1 EDGE
CONNECTOR
TERMINAL 25
TERMINAL 1
T00712A
NIAO01
F1 F2
S8
1
OPEN
4
2 3
S3
1
OPEN
4
2 3
S1
1
OPEN
4
2 3
S7
1
OPEN
4
2 3
S4
1
OPEN
4
2 3
S2
1
OPEN
4
2 3
S6
1
OPEN
4
2 3
S5
1
OPEN
4
2 3