INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-401A
2 - 5
JUMPERS J11 AND J12
Jumpers J11 and J12 are storage posts for extra jumpers.
JUMPER J13
Jumper J13 with pins one and two jumpered connects RS-485
cable shielding (P7, pin one) to chassis ground.
JUMPERS J14 THROUGH J17
Jumpers J14 through J17 allow proper routing of the signals
on the termination module circuit board. These alternate sig-
nals are not related to data communications and are reserved
for future use. For proper RS-232-C and RS-485 operation,
these must be left in the pins one and two jumpered configura-
tion.
Figure 2-5. Loopback Jumper Configuration
Figure 2-6. Handshake Signal Schematic
RXD
T00452A
RXD-A
TXD
CTS-A
CTS
RTS-A
RTS
DB9-2
DB9-3
DB9-7
DB9-8
J1 AND J2
1
2
3
4
5
6
7
8
9
10
11
12
TXD-A
T00453A
+12 V
1
2
2
2
1
1
DSR
DCD
DTR
DB9-6
J6 AND J8
J5 AND J9
J7 AND J10
DB9-1
DB9-4
DB9-5
1
2
J19 AND J20
CTS
DB9-8
NOTES:
1. JUMPERS J20, J8, J9 AND J10
RELATE TO CONNECTOR P6.
2. JUMPERS J19, J6, J5 AND J7
RELATE TO CONNECTOR P5.