INTRODUCTION
SPECIFICATIONS
1 - 6
I-E96-401A
®
SPECIFICATIONS
Refer to Table
for the specifications of the NIMP01 and
NIMP02 termination modules.
Table 1-4. IMP Termination Module Specifications
Property
Characteristic/Value
Power Requirements
+24 VDC, 210 mA maximum current consumption
Communication
Two RS-232-C serial ports, or one RS-232-C port and one RS-485 port.
1 control station serial link
Cable Insulation Specifications:
PVC (UL Rating CL2)
80°C (176°F) at 300 V
Non-PVC (UL Rating PLTC)
90°C (194°F) at 300 V
Mounting
Screw mounts on the field termination panel.
Environmental:
Electromagnetic/Radio
Frequency Interference
Values are not available at this time. Keep cabinet doors closed. Do not
use communication equipment any closer than 2 meters from the cabi-
net.
Operating Temperature
0° - 70°C (32° - 158°F)
Relative Humidity
5% - 90% (
±
5%) up to 70°C (158°F) (noncondensing)
Altitude
Sea level to 3 km (1.86 mi)
Air Quality
Bailey equipment should be operated and stored in a noncorrosive envi-
ronment.
Cooling Requirements
No cooling necessary when used in Bailey cabinets and operated within
environmental limits.
Certification
All termination units are CSA certified as process control equipment for
use in an ordinary (nonhazardous) location.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Содержание infi 90 NIMP01
Страница 2: ......