IMMFP03 MULTI-FUNCTION PROCESSOR
INTRODUCTION
B - 2
I-E96-401A
®
Table B-1. IMMFP03 Dipswitch UUB0
Module Address Settings
Address
Example
Dipswitch Position
(Binary Value)
1
(128)
2
(64)
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
7
Y
0
X
0
0
1
1
1
15
Y
0
X
0
1
1
1
1
31
Y
0
X
1
1
1
1
1
NOTES:
0 = CLOSED or ON, 1 = OPEN or OFF.
1.Y = 0 for normal operation, 1 for special operations (Table
2.X = 0 for Controlway (1 Mbaud), 1 for module bus (83.3 kbaud).
3.Position 2 is reserved. Do not change the s
Table B-2. IMMFP03 Dipswitch UMB1 Options Settings
Position
Setting
Function
1
0
Disable special operations.
1
Enable special operations. Refer to Table
.
2
0
Disable on-line configuration.
1
Enable on-line configuration.
3
0
Enable NVRAM checksum routine.
1
Disable NVRAM checksum routine. This setting is used by development personnel
and should never be used for normal operation. The checksum provides additional
module integrity and should be used whenever the module is controlling a process.
4
0
Enable ROM checksum routine.
1
Disable ROM checksum routine. This setting is used by development personnel and
should never be used for normal operation. The checksum provides additional mod-
ule integrity and should be used whenever the module is controlling a process.
5
0
Enable file system check.
1
Disable file system check.
6
0
Normal.
1
Compact configuration. Moves configured blocks to the top of NVRAM which moves
free space to the bottom (this is known as compacting). Leave switch OPEN and
insert module into MMU. When front panel LEDs 1, 2 and 4 are ON, remove the mod-
ule, put the switch in the CLOSED position and insert the module. The MFP goes into
the configure mode and compacts the configuration.
Leaving this option enabled causes the configuration to be compacted every time the
module is reset, thereby increasing the start-up time. This increase can be substan-
tial if the configuration is large. Therefore, do not leave this option enabled longer
than necessary.
7
0
Normal
1
Initialize NVRAM (erase configuration) - leave switch OPEN and insert the module
into the MMU. When front panel LEDs 1, 2 and 4 are ON, remove the module, put the
switch in the CLOSED position and insert the module. The module is now ready to be
configured. This switch must be CLOSED for normal operation.
8
0
Primary MFP module.
1
Redundant MFP module. When redundancy is used, positions 1 through 7 on the
redundant MFP module are set the same as the primary MFP module. Position 8 is
set to 0 for the primary MFP module and to 1 for the secondary MFP module.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.