IMMFP03 MULTI-FUNCTION PROCESSOR
INTRODUCTION
B - 4
I-E96-401A
®
Table B-6. IMMFP03 Dipswitch LLB3 Option Settings
Position
Setting
Function
Default
Setting
1
—
Not used.
1
2
3
4
5
0
Disable module mounting unit.
1
1
Enable module mounting unit.
6
—
Not used.
0
7
0
Disable data cache.
1
1
Enable data cache.
8
0
Disable instruction cache.
1
1
Enable instruction cache.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.
Table B-7. HW SETUP Socket Settings
Socket Setting
Description
Socket 1 - 16
Insert jumper for IMMFP03 firmware revision E.0. Do not jumper for all other revisions.
Socket 2 - 15
Insert jumper for IMMFP03 firmware revision E.1 and later. Do not jumper for all other
revisions.
Socket 3 - 14
Reserved for future use. Do not jumper sockets.
Socket 4 - 13
Socket 5 - 12
Socket 6 - 11
Socket 7 - 10
Socket 8 - 9
Table B-8. IMMFP03 Jumper Settings for J1, J2, J4 and J5
Jumper
Setting
Function
J1
1
Vertical
Sets the RS-232-C diagnostic port to operate as DCE.
Horizontal Sets the RS-232-C diagnostic port to operate as DTE.
J2
4-3
1 Mbit SRAM device (128k x 8).
4-2
2 Mbits SRAM device (256k x 8).
4-1
4 Mbits SRAM device (512k x 8).
J4
Open
MFT disable jumper. This jumper must remain open for normal operation.
J5
30 VDC
Disconnects Controlway channel B for operation in MMUs that have -30 VDC
(early Network 90).
MODB
Connects Controlway channel B for operation in MMUs that have Controlway
capabilities.
NOTE:
1.This feature is used by Bailey service personnel. The J1 setting does not affect the module during normal operation.
Содержание infi 90 NIMP01
Страница 2: ......