INSTALLATION
INSTALLING THE TERMINATION MODULE
I-E96-408A
2 - 5
5. If the communication cable or power wiring have not been
installed, let the termination module hang out the front of the
TMU several inches. This will allow room to install the commu-
nication cable and power wiring. After the cables are installed,
fully insert the TM until it seats in the cable connector at the
rear of the TMU.
Table 2-3. ICL Cable Applications
Nomenclature/
Description
Application
Connector
Maximum Length
Meters (Feet)
NKLS04 (PVC)
NKLS14 (non-PVC)
Termination cable
Connects the ICL
to the INLIM03
P1
61 (200)
NKLS02 (PVC)
NKLS12 (non-PVC)
Termination cable
Connects the ICL
to the INNIS01
P1
25 (82)
NKCL01 (PVC)
NKCL02 (non-PVC)
Coaxial communica-
tion cable INFI-NET or
Plant Loop
Connects individual
drops on the com-
munication loop
Must connect to an
NKTL01 on each end
2000 (6562), INFI-NET at 10 Mbaud
4000 (13120), INFI-NET at 2 Mbaud
2000 (6562), Plant Loop
NKPL03 (PVC)
NKPL04 (non-PVC)
Twinaxial communica-
tion cable INFI-NET or
Plant Loop
Connects individual
drops on the com-
munication loop
TB1 for Loop 1
TB2 for Loop 2
1000 (3281), INFI-NET at 10 Mbaud
2000 (6562), INFI-NET at 2 Mbaud
2000 (6562), Plant Loop
NKTL01-3
Coaxial adapter cable
Adapts and con-
nects the NKCL01
to the ICL
J1, J2 for Loop 1
J3, J4 for Loop 2
1 (3)
NKTT01
Coaxial cable
Connects an ICL
to an ICL
J1 to J4
800 (2624)
Figure 2-2. ICL Cable Connections to the INLIM03 with Twinaxial Communication Loop
INLIM03
NICL01
NICL01
NKLS04
NKPL03
P1
P2
P3
P1
P1
J1
J1
J1
TB5
TB5
TB4
TB4
IN
LOOP 1
OUT
IN
LOOP 1
OUT
OUT
LOOP 2
IN
OUT
LOOP 2
IN
TB3
TB3
TB2
TB2
TB1
TB1
J3
J3
J2
J2
J4
J4
J2
30
29
28
27
26
25
30
29
28
27
26
25
1 1
1 0
9
8
7
6
5
4
3
2
1
1 1
1 0
9
8
7
6
5
4
3
2
1
T00491A