NETWORK INTERFACE SLAVE MODULE CONFIGURATION (INNIS01)
INTRODUCTION
A - 2
I-E96-408A
®
Table A-1. SW1 Node Addresses/SW2 Ring Numbers
Example Settings
Address
Example
Switch Position
1
2
3
4
5
6
7
8
Binary Value
128
64
32
16
8
4
2
1
1
0
0
0
0
0
0
0
1
64
0
1
0
0
0
0
0
0
250
1
1
1
1
1
0
1
0
Table A-2. Loop Mode Switch (SW3) Settings
Pole
Setting
Function
1
1
IPL/IIL (Bridge or Gateway).
0
PCU/ICI.
2
1
ROM Checksum Enabled
0
ROM Checksum Disabled.
3
1
Test mode; no timeout for handshake failure.
0
Normal operating mode.
4
1
0
Normal operating mode.
1
Busy NAK all Loop Messages.
5
1
0
LED display as defined by SW4.
1
Will toggle on/off group A LEDs if loop 1 is idle or
shorted. Will toggle on/off group B LEDs if loop 2 is
idle or shorted. If both loops are good, normal LED
display as defined by SW4.
6
1
0
Normal operating mode.
1
Diagnostic mode.
7/8
0/0
10 MHz INFI-NET mode.
0/1
2 MHz INFI-NET mode.
1/0
Not used.
1/1
500 kHz Plant Loop mode.
NOTE: 1. Applies to Revision B and later version ROMs. For Revision A ROMs, poles 4 through 6
must be set to 0.