INTRODUCTION
I-E96-408A
4 - 1
SECTION 4 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
Repair procedures are limited to fuse and termination module
(TM) replacement. If the ICL fails, remove it and replace it with
another one.
FUSE REPLACEMENT
If the fuse (F1) opens, replace it with a fuse having an equiva-
lent rating. Table
describes the fuse and lists its Bailey part
number. To replace a fuse:
1. Turn off power to the termination module.
2. Pull on the front cover of the termination module to remove
it.
3. Remove the termination module from the termination
mounting unit (TMU).
4. Remove the blown fuse from its holder (F1).
5. Replace the blown fuse with a 1.0 amp, 250 volt fuse.
6. Return the termination module to its assigned slot in the
TMU.
7. Replace the front cover to the termination module.
8. Turn on power to the termination module.
MODULE REPLACEMENT
If you determine that the ICL is faulty, replace it with a new
one.
Do not
try to repair the module; replacing components
may affect the module performance and certification. Table
contains a list of recommended spare parts.
Table 4-1. Recommended Spare Parts List
Description
Part Number
Fuse, 1.0A/250V
Bailey P/N 194776A11001