TROUBLESHOOTING
FUNCTION CODE 150 PROBLEM REPORTS
6 - 6
I-E96-322A
®
FUNCTION CODE 150 PROBLEM REPORTS
Problem reports generated by function code 150 are I/O error
reports (report type 12). Function code 150 problem reports
generate one error type: Error type 1 - No response/wrong type
(refer to Tables
and
TROUBLESHOOTING HARDWARE FAILURES
Effectively troubleshoot a hardware failure by using the flow-
charts to isolate the failure (see Figures
and
). After
locating the failure, refer to the text or other reference docu-
ments for more information about the failure and the correc-
tive action. Contact the manufacturer for control loop process
3 - Channel
failure/out of
range
(continued)
Any fatal servo output failure:
Nonredundant servo 1 outputs (S2=0) and
both servo 1 coils failed.
Nonredundant servo 2 outputs (S2=1) and
both servo 2 coils failed.
Redundant servo outputs (S2=2 or 3) and all
servo coils failed.
I/H converter mode and output (S2=4 or 5) 1
coil 1 failure.
1. Refer to quality of FC 55 outputs N+2
through N+5 to isolate the error.
2. Check output field connections and
servo valve or I/H converter. If error
persists, replace IMHSS03 or indicated
servo valve or I/H converter.
9 - Input
failure
Any nonfatal LVDT failure:
Redundant LVDTs, LVDT 1 as primary
(S3=2), and any LVDT 1 error.
Redundant LVDTs, LVDT 1 as primary
(S3=2), and any LVDT 2 error.
Redundant LVDTs, LVDT 2 as primary
(S3=3), and any LVDT 1 error.
Redundant LVDTs, LVDT as primary
(S3=3), and any LVDT2 error.
I/H mode (S3=4 or 5) and any LVDT1 error.
1. Refer to FC 55 output N+7 to isolate
error.
2. Check LVDT connections. If error
persists, replace indicated LVDT or
IMHSS03.
Module A/D error. Error will also be indicated
in FC 55 output N+6.
Replace IMHSS03.
12 - Output fixed Any nonfatal servo output failure:
Nonredundant servo 1 outputs (S2=0) and
any servo 1 single coil failure (1 or 2).
Nonredundant servo 2 outputs (S2=1) and
any servo 2 single coil failure.
Redundant servo outputs (S2=2 or 3) and
one, two or three coil failures.
1. Refer to quality of FC 55 outputs N+2
through N+5 to isolate the error.
2. Check servo field connections and
servo valve. If error persists, replace
IMHSS03 or indicated servo valve.
Contingency error. Error will also be indicated
in FC 55 output N+6.
Check field connections. Check for valve
errors.
Table 6-2. Function Code 55 Module Problem Report
(continued)
Error Type
Module Error
Corrective Action