INSTALLATION
INITIAL IMHSS03 DIPSWITCH SETTINGS
3 - 6
I-E96-322A
®
to set S2 for manual LVDT calibration
.
Refer to
Table
for S2 dipswitch settings.
Dipswitch S3 - Controller Gain
Dipswitch S3 is an eight-pole dipswitch that sets the controller
gain. This dipswitch is ignored if the module is configured with
function code 55. Set the controller gain to one.
This amplifier compares position demand to position feedback
and outputs the difference of those signals. The controller gain
affects the response of the control loop. If the module is config-
ured as an IMHSS02 module using function code 150, this
dipswitch must have an initial setting. Refer to
CONTROLLER
TUNING
in
to initially set S2 for manual controller
gain tuning. Refer to Table
for S3 dipswitch settings.
Table 3-2. Dipswitch S2, Demodulator Gain
Gain
Dipswitch Pole
User Setting
1
2
3
4
5
6
7
8
2.0
1
1
1
1
1
1
1
0
5.5
1
1
1
1
1
1
0
1
10.0
1
1
1
1
1
0
1
1
21.1
1
1
1
1
0
1
1
1
48.8
1
1
1
0
1
1
1
1
72.0
1
1
0
1
1
1
1
1
100.9
1
0
1
1
1
1
1
1
152.0
0
1
1
1
1
1
1
1
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table 3-3. Dipswitch S3, Controller Gain
Gain
Dipswitch Pole
User Setting
1
2
3
4
5
6
7
8
1.00
1
1
1
1
1
1
1
0
2.00
1
1
1
1
1
1
0
1
5.00
1
1
1
1
1
0
1
1
10.50
1
1
1
1
0
1
1
1
13.35
1
1
1
0
1
1
1
1
14.46
1
1
0
1
1
1
1
1
18.10
1
0
1
1
1
1
1
1
20.52
0
1
1
1
1
1
1
1
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.