CALIBRATION
MANUAL TUNING (FUNCTION CODE 55)
4 - 6
I-E96-322A
®
•
The servo valve or I/H converter (for turbine hydraulic sys-
tem) must be in the controlling position and functioning
properly.
•
The multi-function processor module has function code 55
in its configuration.
To manually tune the demodulator gain:
1. Go to S15 and set it to 1 so that volts are the display units
on output block N.
2. Go to the block specified in S6, and set it to 0%.
3. Observe the LVDT secondary voltage at output block N and
wait until the value stops changing.
4. If the 0% position value of output block N is greater than
-8.5 V, then increase the value of the demodulator gain by set-
ting specification S16 to the next higher gain and repeat
Step 3.
5. When the 0% value is less than -8.5 V, decrease the
demodulator gain to the next lower setting.
6. Go to the block specified in S6, and set it to the 100%
position.
7. Observe the LVDT secondary voltage at the output block N
and wait until the value stops changing.
8. If the 100% position at output block N is greater than
8.5 V, then decrease the value of the demodulator gain by set-
ting specification S16 to the next lower gain and repeat Step 7.
9. If the demodulator gain has been changed from the value
determined in Step 4:
a. Go to the block specified in S6, and tune it to 0%.
b. Observe the LVDT secondary voltage at output block N
and wait until the value stops changing. When the value
stops changing, read the final value and verify that it is
acceptable. None of the LVDT 0% values should be greater
than -5 V and none of the LVDT 100% values should be
less than 5 V.
10. If there are redundant LVDT transformers, repeat this pro-
cedure for the backup LVDT transformer. Select the backup by
changing the value of S3 to select the other LVDT transformer.
Use the lowest of the two gains for redundant LVDT transform-
ers. Verify that both LVDT transformers are still within range.
If any LVDT transformer is not within range, refer to